***************************************************** ECpv2 release text ***************************************************** ***************************************************** Version 1.00.0 based on ECpv Verion 1.86.0 ***************************************************** 1- Support of Analogue IO modules EX04AIO and EX04AIS. 2- Analogue sensors supported via the Analogue IO modules. 3- Fuel level sensor support added. 4- Fuel level alarm added. 5- Support of Fuel pressure sensor readout added. 6- Support of BDSensor DCL531 added. 7- P/Q Mains reference manipulation via RRCR Analogue scheme added. 8- Load meter support added. 9- Load meter data made possible to use for control routine. 10- Command timer added. 11- Command panel interface added. 12- Support of multiple inverter clusters via Huawei Smartloggers, Sungrow COM100E or SMA InverterManagers. ***************************************************** Version 1.01.0 based on version 1.00.0 ***************************************************** 1- Support of WindMeter from Soluzione Solare added. 2- Windspeed now displayed with one decimal. 3- Settings for Panel degradation, DC losses and AC losses are added to the PV generating capacity scheme. 4- SDMO APM802 support added. 5- Chint 14_36kW support added. 6- Chint SCA 18_36kW support added. 7- Sofar 80_136kW support added. ***************************************************** Version 1.02.0 based on version 1.01.0 ***************************************************** 1- Weekday added to Command timers. ***************************************************** Version 1.02.1 based on Version 1.02.0 ***************************************************** 1- Config read fail could be provoked unexpectedly. ***************************************************** Version 1.02.2 based on Version 1.02.1 ***************************************************** 1- Eventlog handling updated. ******************************** Version 1.03.0 based on version 1.02.2 ******************************** 1- Support of PV control selection "P ONLY" added. 2- Support of inverter acquisition when using the Sungrow COM100E protocol added. 3- Support of meteo acquisition from a PC-4 when using the Sungrow COM100E protocol added. 4- Update of SPM32/SPM33 meter handling in case of presence of PTs. ******************************** Version 1.04.0 based on version 1.03.0 ******************************** 1- Support of SGC120/121 2- Support of SunMeter Pro WIND (with one decimal display). 3- BOM offset added 4- DFUN DFPM93 power meter support added 5- WEG 750SIW inverter protocol added. 6- All PWMet sensors are now supported. 7- DEYE inverter protocol added. 8- Acuvim L protocol updated. ******************************** Version 1.04.1 based on version 1.04.0 ******************************** 1- Menu split-up. ******************************** Version 1.04.2 based on version 1.04.1 ******************************** 1- ABB TRIO protocol handling updated. ******************************** Version 1.05.0 based on version 1.04.2 ******************************** 1- EClogic alarms added. 2- EClogic timers added. ******************************** 1.05.1 based on version 1.05.0 ******************************** 1- WEG protocol updated. ******************************** Version 1.06.0 based on version 1.05.1 ******************************** 1- Sensitivity handling of Modbus Master alarms added. ******************************** Version 1.07.0 based on version 1.06.0 ******************************** 1- Inverter power production deviation alarm support added. 2- Inhinitation of inverter communication alarms based on night condition and/or low POA condition support added. 3- Lettel MCX-34V support added. ***************************************************** Version 1.07.1 based on version 1.07.0 ***************************************************** 1- Modbus TCP on Power meter and IO communication updated. 2- Modbus Master sensitivity scheme for superior loggers like Smartlogger and COM100E updated. 3- EClogic Modbus Events added. 4- Change made to Acuvim L handling. ***************************************************** Version 1.07.2 based on version 1.07.1 ***************************************************** 1- Correction made to Acuvim L handling. ******************************** Version 1.07.3 based on version 1.07.2 ******************************** 1- Update made to handling of "Control ID/IP" readings. ******************************** Version 1.07.4 based on version 1.07.3 ******************************** 1- SunSpec handling updated. 2- Update made to Alarm Signal handling. ******************************** Version 1.07.5 based on version 1.07.4 ******************************** 1- TCP Client handling updated. ******************************** Version 1.07.6 based on version 1.07.5 ******************************** 1- TCP Client update made in 1.07.5 enhanced. ******************************** Version 1.08.0 based on version 1.07.6 ******************************** 1- Datakom D300_500_700 support added. 2- PV generating capacity is now set to 0kW in case it is night time and the generating capacity method is set to OFF. ******************************** Version 1.09.0 based on version 1.08.0 ******************************** 1- InteliGen_4_200 support added. 2- InteliMains_210 support added. 3- Rica RK200 and RK220 support added. ******************************** Version 1.09.1 based on version 1.09.0 ******************************** 1- The buttons for going to inverter data 17-32 was not taking inverter cluster into consideration causing the page to be hidded when not supposed to. 2- Mains readings was not shown on Overview page if it came from "PV_COMM". 3- Mains readings was not shown on Overview page if it came from "MODBUS PAGE 03". 4- DG readings was not shown on Overview page if it came from "MODBUS PAGE 03". ******************************** Version 1.09.2 based on version 1.09.1 ******************************** 1- Update made to reboot handling. ******************************** Version 1.10.0 based on version 1.09.2 ******************************** 1- SMA DataManager support added. 2- Some Mains counter elements where not saved with the correct label. ******************************** Version 1.10.1 based on version 1.10.0 ******************************** 1- SMA DataManager support updated. ******************************** Version 1.11.0 based on version 1.10.1 ******************************** 1- INVT XG support added. 2- Reactive power control added for Sofar 80-136kW handling. 3- Start/stop command added for Sofar 80-136kW inverter handling. ******************************** Version 1.11.1 based on version 1.11.0 ******************************** 1- SMA DataManager support updated. ******************************** Version 1.12.0 based on version 1.11.1 ******************************** New features: 1- Acrel ADL3000-E support added. 2- Increased from 4 to 8 EClogic alarms. ******************************** Version 1.12.1 based on version 1.12.0 ******************************** 1- All "No alarm" logs generated at power up are now suppressed. 2- Load icon and busbar lines is now green in case genset or grid is connected. 3- SMA Datamanager number of decimals to use for control commands can now be set via settings. 4- Update made for Ginlong Solis. ******************************** Version 1.12.2 based on version 1.12.1 ******************************** 1- EClogic alarm texts handling updated. 2- Modbus Slave handling updated. 3- Modbus data for total number and number of secondary inverters present in the plant where not correct. ******************************** Version 1.12.3 based on version 1.12.2 ******************************** 1- NTP sync alarm is now self-acknowledging. ******************************** Version 1.12.4 based on version 1.12.3 ******************************** 1- Smartlogger handling updated. ******************************** Version 1.12.5 based on version 1.12.4 ******************************** 1- Active power for individual phases included in the Huawei power meter protocol support. ******************************** Version 1.13.0 based on version 1.12.5 ******************************** 1- Selection for displaying the relative or total load and grid and genset powers. ******************************** Version 1.13.1 based on version 1.13.0 ******************************** 1- Update made to the Carlo Gavazzi EM300 handling. 2- Update made to the Datakom D300-700 handling. ******************************** Version 1.13.2 based on version 1.13.1 ******************************** 1- The "Sync-SR" routine is updated. ******************************** Version 1.14.0 based on version 1.13.2 ******************************** 1- Support of Selec MFM384 added. 2- WEG SIW750 handling updated. ************************************************ Version 1.14.1 based on version 1.14.0 ************************************************ 1- Default setup for COM2 and COM3 changed. 2- Default setup for NTP changed. 3- DSE GenComm. support updated. ******************************** Version 1.15.0 based on version 1.14.1 ******************************** 1- Support for SAH XY-MD02 added. 2- Deye handling updated. 3- SMA DataManager added as grid power meter selection. ******************************** Version 1.16.0 based on version 1.15.0 ******************************** 1- Support for Cummins MCM3320 added. 2- Support for Cummins Sices MC200/MC400 added. 3- Option of using fixed CT/VT settings for SPM32 and SPM33 added. ******************************** Version 1.16.1 based on version 1.16.0 ******************************** 1- Grid readings via SMA DataManager updated. ******************************** Version 1.16.2 based on version 1.16.1 ******************************** 1- Update made to sensor handling. 2- Deye inverter handling updated. ******************************** Version 1.16.3 based on version 1.16.2 ******************************** 1- Clock handling updated. ******************************** Version 1.17.0 based on version 1.16.3 ******************************** 1- Spot price support added. 2- Solax X3-MEGA and G2G3-FORTH support added. ******************************** Version 1.18.0 based on version 1.17.0 ******************************** 1- Include PV energy while grid parallel in CO2 saving calculation. 2- Same cosphi option added to Mains Q CTRL. 3- Limit option for RRCR added. 4- Mains Reading option added to the PV "kW Origin" ******************************** Version 1.19.0 based on version 1.18.0 ******************************** 1- Support added for Lufft WS200 weather station ******************************** Version 1.20.0 based on version 1.19.0 ******************************** 1- Support added for Ingeteam 3Play inverter ******************************** Version 1.21.0 based on version 1.20.0 ******************************** 1- Support added for LogicsPowerAMR PYRA 300V MeteoSensor 2- Update made to inverter cluster capacity editing ******************************** Version 1.22.0 based on version 1.21.0 ******************************** 1- Support added for Siemens Smart 7kt0310 Power Meter 2- Added PID control option for PV inverter power set points 3- Changed Growatt PV inverters Power factor calculation ******************************** Version 1.23.0 based on version 1.22.0 ******************************** 1- Support added for IME Nemo96EA powermeter ******************************** Version 1.24.0 based on version 1.23.0 ******************************** 1- Added EClogic function to overwrite PV Reference 2- DNP3 protocol adjustments ******************************** Version 1.25.0 based on version 1.24.0 ******************************** 1- Added support for Comap InteliGen 1000 Genset Powermeter 2- Encombi DG Group power meter protocol enables grouping of mulitple Gensets under one ECpv2 in order to combine more than 16 Gensets per site. ******************************** Version 1.26.0 based on version 1.25.0 ******************************** 1- Option to turn off unused Modbus frames from Power meters. 2- Corrections to Siemens 7kt0310 and AccuvimII power meter protocols. ******************************** Version 1.27.0 based on version 1.26.0 ******************************** 1- Support for Afore PV inverter added. 2- EClogic Function added to overwrite Mains PV control mode. 3- Fixed a problem that caused the PV reference to be doubled. ******************************** Version 1.27.1 based on version 1.27.0 ******************************** 1- PV PREF/QREF can now be written to via Modbus page02. 2- IO socket alarm log handling improved were not handled correctly. 3- Update made to the DFPM93 support. ******************************** Version 1.27.2 based on version 1.27.1 ******************************** 1- Update made to the DFPM93 support. ******************************** Version 1.27.3 based on version 1.27.2 ******************************** 1- Update made to the SevenSensor support. ******************************** Version 1.28.0 based on version 1.27.3 ******************************** 1- Support for WEG MMW03 power meter added. ******************************** Version 1.29.0 based on version 1.28.0 ******************************** 1- Support for Growatt VPP PV inverter added. 2- Support for Meier Energy CMM62 power meter added. ******************************** Version 1.29.1 based on version 1.29.0 ******************************** 1- SevenSensor MeteoSensor protocol updated to newest version. ******************************** Version 1.29.2 based on version 1.29.1 ******************************** 1- Start/stop of PV via EClogic added. 2- Removed the ability to send E-mails. ******************************** Version 1.30.0 based on version 1.29.2 ******************************** 1- Support added for DMeters DM1000 Power meter. ******************************** Version 1.30.1 based on version 1.30.0 ******************************** 1- Fixed the addressing for Schneider PM2XXX series power meters. ******************************** Version 1.31.0 based on version 1.30.1 ******************************** New features: 1- Support for commands via ECapi added. ******************************** Version 1.32.0 based on version 1.31.0 ******************************** New features: 1- Support for RICA330 added. 2- Support for Meatrol ME337 added. 3- Support for Crown Voltmore added. ******************************** Version 1.33.0 based on version 1.32.0 ******************************** 1- Support for Growatt ShineMaster X added. 2- Support for Legrand EMDX3 Power meter added.